摘要: 以三峡水利枢纽地下水电站开关站(GIS)设备的雷电冲击电压试验为例,对试验原理、设备和试验程序进行了详细描述。在试验过程中出现了放电现象,同时发现大电容量的试品在进行雷电冲击电压试验的波形选择和在GIS设备的安装施工中也出现了一些问题。为此,针对上述出现放电现象的原因及其他一些问题进行了分析研究,研究结果可以为大型气体绝缘开关站的雷电冲击电压试验提供借鉴与指导。
关键词: GIS, 雷电冲击电压试验, 地下电站, 三峡水利枢纽
Abstract:
Taking lightning hit withstand test of GIS for the underground power station of Three Gorges hydro-junction as a case, the principle, equipment and procedures of test are described in detail. The electric discharge phenomena occurred in the test process, and the problems existed in waveform selection for the test devices of large electric capacity during the test and installation of GIS. The causes for the discharge and other problems were analyzed. The results could provide reference and guide GIS lightning hit test for power stations.
Key words: GIS, lightning impulse withstand test, underground power station, Three Gorges Reservoir